Cable Size Calculator, Voltage Drop and kW to Amps

Calculators for electricians

Last updated 17 November 2026.

Size a twin and earth cable, check its voltage drop and convert kW to amps in one place. On a single phase 230V supply, amps = watts ÷ 230, so a 3kW load draws 13.0 amps. Voltage drop = mV/A/m × amps × metres ÷ 1000. The calculators below do the sums for you.

Cable size  ·  Voltage drop  ·  kW to amps  ·  Ratings table

Cable size calculator

For single phase 230V circuits in flat twin and earth, 1mm² to 16mm². Enter the load, the run length and how the cable is installed.

Letters and numbers are the BS 7671 reference methods. Ceiling means above a plasterboard ceiling under thermal insulation. Stud wall means a wall with thermal insulation, with the cable touching or not touching the inner surface.

2.5mm²twin and earth
20Aprotective device
27Acable rating
3.9%voltage drop

2.5mm² twin and earth on a 20A device. Rated 27A installed this way, voltage drop 9.0V (3.9 percent) over 25 metres. Sized up from 1.5mm² to keep the voltage drop within 5 percent.

Assumes 30°C, no grouping with other cables and copper flat twin and earth to BS 7671 Table 4D5. The device is the next standard MCB size at or above the load. A starting point for your design, not a substitute for the I.S. 10101 calculation.

Voltage drop calculator

Check a cable you have already chosen. Single phase 230V, flat twin and earth.

9.0Vvoltage drop
3.9%of 230V
221.0Vat the far end

Within the 5 percent limit.

kW to amps and amps to kW

13.0Afrom 3 kW
2.99kWfrom 13 amps

Use a power factor of 1 for heaters, kettles, immersions and other resistive loads. Motors, pumps and some LED drivers sit lower, often 0.8 to 0.95, so check the nameplate. For three phase, amps are per phase.

How the cable size calculator works

  • ✓Design current. Your load in amps, or kW ÷ 230 at power factor 1.
  • ✓Protective device. The next standard MCB size at or above the design current: 6, 10, 16, 20, 25, 32, 40, 50 or 63 amps.
  • ✓Current rating. The smallest twin and earth whose rating for your installation method is at least the device rating.
  • ✓Voltage drop. If that cable drops more than your limit over the run, it steps up a size until it passes.

It does not apply grouping, ambient temperature or thermal insulation correction beyond the installation method you pick, and it does not check earth fault loop impedance or disconnection times. Those are part of the full design.

Twin and earth current ratings and voltage drop

BS 7671 Table 4D5, 70°C thermoplastic flat twin and earth, copper conductors, 30°C ambient. Amps for each installation method.

Size Clipped direct (C) Conduit on wall (B) Conduit in insulated wall (A) Ceiling, insulation up to 100mm Ceiling, insulation over 100mm mV/A/m
1mm² 16 13 11.5 13 10.5 44
1.5mm² 20 16.5 14.5 16 13 29
2.5mm² 27 23 20 21 17 18
4mm² 37 30 26 27 22 11
6mm² 47 38 32 34 27 7.3
10mm² 64 52 44 45 36 4.4
16mm² 85 69 57 57 46 2.8

Ratings fall further when cables are grouped together, run in hotter spaces or buried in insulation. Wherever you can, keep cable out of thermal insulation.

Amps for common loads

At power factor 1. Single phase 230V unless stated.

Load Current
1kW 4.3A
2kW 8.7A
3kW 13.0A
3.68kW 16.0A
7.36kW 32.0A
9.2kW 40.0A
11kW, three phase 15.9A per phase
22kW, three phase 31.8A per phase

Pricing the cable for a job?

We carry twin and earth, armoured, flex and data cable at our trade counter in Greenogue, just off the N7 and well positioned for the M50. Cable is sold in store only, not online.

More on the ranges in our guide to electrical cable in Ireland.

Questions

How do I convert kW to amps?

On a single phase 230V supply, amps = watts ÷ 230 for a heating load (power factor 1). A 3kW load draws 13.0 amps. On a three phase 400V supply, amps per phase = watts ÷ (1.732 × 400). For motors and other loads with a power factor below 1, divide by the power factor as well.

How many amps is 7kW?

About 30.4 amps on a single phase 230V supply, or 10.1 amps per phase on a three phase 400V supply, assuming a power factor of 1.

What size cable do I need for a 32 amp circuit?

It depends on how the cable is installed and how long the run is. Clipped direct, 4mm² flat twin and earth is rated 37 amps in BS 7671 Table 4D5, which covers a 32 amp device. Above a ceiling under more than 100mm of insulation the same circuit needs 10mm², rated 36 amps. Then check the voltage drop for the length. The calculator on this page does both steps.

How do you calculate voltage drop?

Multiply the cable's voltage drop figure in mV/A/m by the current and the one way length in metres, then divide by 1000. For 2.5mm² twin and earth (18 mV/A/m) carrying 20 amps over 25 metres: 18 × 20 × 25 ÷ 1000 = 9.0 volts, which is 3.9 percent of 230V.

What voltage drop is allowed in Ireland?

I.S. 10101, the national wiring rules, sets out voltage drop as a formula to calculate rather than a table to look up, and the limit depends on the circuit and the design. Many designers work to 3 percent for lighting and 5 percent for other circuits, the figures used in the UK rules, BS 7671. Check the limit that applies to your installation in I.S. 10101, and set it in the calculator.

Are these I.S. 10101 figures?

No. The current ratings and voltage drop figures are the published BS 7671 Table 4D5 values for flat twin and earth cable at 30°C. I.S. 10101 is built on the same European method, but always check the rating for your installation method, grouping and temperature in I.S. 10101. Electrical work in Ireland must be designed, tested and certified by a Registered Electrical Contractor.

Where can I buy twin and earth cable?

At our trade counter in Greenogue, Rathcoole, just off the N7. Cable is sold in store only, not online. Call 01 401 9907 or email sales@shamrockelectrical.ie for a trade price, or open a trade account.

Current ratings and voltage drop figures are the published BS 7671 Table 4D5 values for flat twin and earth at 30°C. Results are a guide for qualified electricians and are not a substitute for a design to I.S. 10101 by a Registered Electrical Contractor. Last updated 17 November 2026. Questions? Call 01 401 9907 or email sales@shamrockelectrical.ie.